Return to Top Button
Back to Meter GuideGet Help or Quote

A highly flexible (6 12, 24, 36, or 48 CT inputs) revenue-grade, multi-point electrical meter for regulated markets.

  • Accuracy: ANSI C12.20, Class 0.5
  • Electrical Inputs: 12, 24, 36, or 48  
  • Configuration: Any approved combination of single, two, or 3-element meter points
  • CTs: 80mA Solid Core
  • Voltage: 2 VRef, 300V max
  • Pulse Inputs: Up to 48
  • Approvals: Measurement Canada, NYPSC, Maryland PSC, CDFA

Features and Specifications

Device Configuration

  • Any approved combination of single, two, or 3-element meter points

Supported CTs

  • 80mA Solid Core CTs
  • Up to 300 ft (100 m) from meter with 22 AWG wire pairs

Voltage Connections

  • 120V to 277V service voltages

Communication Options

  • Ethernet (native)

4-quadrant Meter Measurement (Total and Per Phase)

  • Active, Reactive & Apparent Power
  • Peak W and VA Demand
  • PF and phase angles
  • Irms, Vrms

General

  • Up to 48 pulse inputs to connect other metering devices
  • Dual Service voltages up to 277V with no external PTs
  • On-board Web server and large 4x20 Liquid Crystal Display for local readings
  • Multi-homing for reporting to multiple management services
  • Innovative, 2-part meter and meter base design — sealable for tamper-evident compliance
  • Integrated self-shorting CT connection modules
  • Built-in WIFI Access Point
  • Cloud-based meter management

Reporting and Communications

AMR via FTP data push over IP or (optional) MODEM

  • Plain text CSV file
  • Measurement Interval: 1 to 60 minutes
  • Reporting interval: once/day or every N minutes

Logged Measurements for AMR (interval and register)

  • Wh delivered & received
  • VARh delivered & received
  • VAh
  • Peak W & VA Demand
  • Present W & VA Demand
  • Peak Current
  • Vrms

Ethernet Interface

  • 10/100BaseT Full Duplex
  • DHCP Client or static IP address
  • Passive FTP port 21
  • NTP port 123
  • Modbus TCP/IP port 502
  • BACnet IP port 47808
  • HTTP port 80

WIFI Access Point

  • 802.11 b.g.n 2.4 GHz

Other

  • BAS Integration bia BACnet IP, Modbus TCP/IP
  • On-board Web server and Liquid Crystal Display for local readings

Support and Downloads

Meter Installation

Meter Configuration